Design an I/O Power Supply from the Omron NX Bus

Design an I/O Power Supply from the Omron NX Bus

Greg Haley | November 27th, 2018

In my previous blog, "What is an Omron NX Power Module and Do You Need One?," we discussed what an Omron NX power supply module was and why it was necessary. In this blog, we will go more in depth on how to design and specify the actual power supply needed for a particular system.

First, we address a few disclaimers:

  • This assumes an additional power supply unit is connected to the right side of the CPU because one or more modules require power from the NX bus.
  • The total current needed by the I/O modules on the NX bus cannot, and must not, exceed the total current output of the unit supplying the power.
  • The voltage drop of the I/O circuits inside each NX module that get power from the NX bus must be within the specification of the voltage drop in the I/O power supply.

There are 4 Steps to follow in order to design the power supply.

  1. Calculate the total current and voltage drop. Calculate the total current consumption and voltage drop in each power supply of the NX units connected to the CPU as well as the CPU itself.
  2. Add the voltage and current drops of each module together. Starting from the left (next to the first I/O Power Supply module), add together the voltage drops and current consumption of each NX module. Omit any module that does not draw power from the NX Bus.
  3. Compare the voltage and current loads to the spec of the I/O Power Supply Unit. If the addition of an NX module causes the total current consumption of the I/O units to exceed the current or voltage capacity of the additional I/O power supply - then add another I/O power supply unit to the left of the module that put the total over the limit.
  4. Repeat until all modules are accounted for. Repeat steps 2-4 starting with the first module to the right of the additional I/O Power Supply module. Stop when all modules are accounted for.

Here is an image from the NX201 manual to help illustrate this process:

Design%20an%20IO%20Power%20Supply%20from%20the%20Omron%20NX%20Bus.PNG

For details on how to calculate the current consumption and voltage consumption of a module, refer to the NX201 manual pages 4-13 and 4-15, respectively. This design process can be found on page 4-11 of the NX201 manual.

Profile picture for user Greg Haley

Greg Haley

LinkedIn

Greg received his degree in Mechanical Engineering from the University of Florida. He has spent his entire professional career working in the automation industry, including as a consultant building an automated manufacturing system, 4 years as a Field Engineer in the automated test industry, and most recently, a Motion/Robotics solution provider with Cross Company.